      What are the technical requirements for the installation of UPS power batteries? There are certain requirements for the installation of UPS power batteries. If the installation does not meet the specific requirements, safety failures may easily occur. Before installing and using UPS batteries, please check the safety valve of each battery one by one. Is it firm? If it is loose, tighten it immediately. It is prohibited to damage the surface coating of the battery rack components during installation.

      What are the technical requirements for UPS power battery installation?

      ① The UPS power battery must be installed in a dedicated room. Doors, windows, walls, wooden frames, ventilation equipment, etc. must be coated with acid-resistant paint for protection, and the floor must be paved with acid-resistant bricks and maintained at a certain temperature. There should be water and sewers indoors.

      ② The UPS power battery room should be kept tight, and the glass on doors and windows should be frosted glass or painted with white paint.

      ③The installation location of lighting fixtures must be convenient for maintenance. The wires or cables used should be acid-resistant lamps and switches.

      ④ Heating equipment is not allowed to have flange connections and valves indoors, and the distance from the electric appliance must not be less than 750 meters.

      ⑤The air duct opening should be equipped with a filter and an independent ventilation duct.

      ⑧It is not difficult to install charging equipment in the battery room.

      ⑦The installation of fixed open-type UPS power battery wooden bench should meet the requirements.

      ⑧The thermometer, density meter, and liquid level line should be located on the side that is easy to inspect.

      UPS power battery installation precautions

      1. It is best to store the UPS battery upright, which is more conducive to preventing battery fluid leakage. In order to prevent the impact of leakage, an anti-corrosion pad can also be placed on the bottom of the battery.

      2. It is best to keep a distance of about 5-10mm between UPS batteries.

      3. The battery needs to be kept in a stable battery rack or battery cabinet.

      4. If the UPS power supply has a large number of batteries and a large current, it is recommended to install a copper transfer bar in the battery rack or battery cabinet to facilitate wiring and prevent accidents caused by thick cables pulling the batteries.

      5. When there are earthquake resistance requirements, the earthquake resistance facilities should comply with relevant regulations and be strong and reliable.

      6. The battery should be kept away from direct sunlight, cannot be placed in a closed container, and cannot be placed in an environment with radioactivity, infrared radiation, ultraviolet radiation, organic solvent gases and corrosive gases.

      7. UPS power batteries leave the factory in a wet charged state. During transportation and installation, they must be handled carefully to prevent short circuits.


    Read recommendations:

    Lithium Battery LQ-1220

    Break through the energy density of the battery.wall-mounted energy storage battery wholesale

    Basic requirements for ship batteries

    14250 battery wholesale

    NiMH No. 7

    r03 battery.Why do lithium batteries need BMS? The role of BMS in lithium battery protection boards

    Return to List

    R03 Carbon battery.Current status and core technologies of echelon utilization of retired lithium ir

    Relevant News